10-28 (32) 2UEA001270 Rev. F ACS2000 User manual
Chapter 10 - Troubleshooting and maintenance
5 Remove the plexiglas air plenum
by removing the six screws.
Screw type: M6 socket-head
screw
Required tool: 10 mm socket
When working on the AFE, first pull
out the air pressure tube at the
bottom of the panel.
6 Unplug fiber optic cables and
control wiring connector from the
front of the phase module.
Carefully position cables to prevent
damaging them when changing the
phase module.
7 Remove the screws on the left/right
side of the phase module.
Screw type: M10 socket-head
screw
Required tool: 10 mm socket
8Frame 1 - Insert the module tray
into the cabinet along the lower
sides of the phase module.
Slide the phase module tray
tool in, until it makes contact
with the metal flange on both
sides of the NP frame.
Remove 6 screws
Phase module
screws

Table of Contents