EasyManua.ls Logo

ABB ACS850 - Page 273

ABB ACS850
370 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Additional parameter data 273
14.19 DIO5 out src Bit pointer 32 - - Ref running
14.22 DIO6 conf enum 16 0…1 - Output
14.23 DIO6 out src Bit pointer 32 - - Fault
14.26 DIO7 conf enum 16 0…1 - Output
14.27 DIO7 out src Bit pointer 32 - - Alarm
14.30 DIO8 conf enum 16 0…1 - Output
14.31 DIO8 out src Bit pointer 32 - - Ext2 active
14.34 DIO9 conf enum 16 0…1 - Output
14.35 DIO9 out src Bit pointer 32 - - At setpoint
14.38 DIO10 conf enum 16 0…1 - Output
14.39 DIO10 out src Bit pointer 32 - - Zero speed
14.42 RO1 src Bit pointer 32 - - Ready relay
14.43 RO1 Ton UINT32 16 0…3000 s 0.0 s
14.44 RO1 Toff UINT32 16 0…3000 s 0.0 s
14.45 RO2 src Bit pointer 32 - - RunningRelay
14.48 RO3 src Bit pointer 32 - - Fault(-1)
14.51 RO4 src Bit pointer 32 - - P.06.02.02
14.54 RO5 src Bit pointer 32 - - P.06.02.04
14.57 Freq in max REAL 16 3…32768 Hz 1000 Hz
14.58 Freq in min REAL 16 3…32768 Hz 3 Hz
14.59 Freq in max scal REAL 16 -32768…32768 - 1500
14.60 Freq in min scal REAL 16 -32768… 32768 - 0
14.61 Freq out src Val pointer 32 - - P.01.01
14.62 Freq out max src REAL 16 0…32768 - 1500
14.63 Freq out min src REAL 16 0…32768 - 0
14.64 Freq out max sca REAL 16 3…32768 Hz 1000 Hz
14.65 Freq out min sca REAL 16 3…32768 Hz 3 Hz
14.66 RO6 src Bit pointer 32 - - C.FALSE
14.69 RO7 src Bit pointer 32 - - C.FALSE
14.72 DIO invert mask Pb 16 0b0000000000 …
0b1111111111
- 0b0000000000
15 Analogue outputs
15.01 AO1 src Val pointer 32 - - Current %
15.02 AO1 filt time REAL 16 0…30 s 0.100 s
15.03 AO1 out max REAL 16 0 … 22.7 mA 20.000 mA
15.04 AO1 out min REAL 16 0 … 22.7 mA 4.000 mA
15.05 AO1 src max REAL 32 -32768…32768 - 100.000
15.06 AO1 src min REAL 32 -32768…32768 - 0.000
15.07 AO2 src Val pointer 32 - - Speed %
15.08 AO2 filt time REAL 16 0…30 s 0.100 s
15.09 AO2 out max REAL 16 0 … 22.7 mA 20.000 mA
No. Name Type
Data
len.
Range Unit
Default
(Factory macro)

Table of Contents

Other manuals for ABB ACS850

Related product manuals