6.2.5 Problem starting or connecting the FlexPendant
Description
The FlexPendant is not responding, either completely or intermittently.
No entries are possible, and no functions are available.
Note
If protective gloves are used, these must be compatible with touchscreens when
using the FlexPendant.
The FlexPendant starts but does not display the main interface.
xx1900000917
Required test equipment
Equipment needed for troubleshooting:
NoteEquipment
Multimeter
Insulating gloves
3HAC059896-009, 3HAC063898-009,
3HAC072448-009
Circuit diagram - OmniCore C30, Circuit dia-
gram - OmniCore C30 for IRB 14050, Circuit
diagram - OmniCore C30 for CRB 15000
Preparations
Action
Make sure that the controller is switched on.1
Wait 30 s - 1 min to enable start-up sequence.
Check the FlexPendant for errors and warnings.2
Continues on next page
Product manual - OmniCore C30 517
3HAC060860-001 Revision: P
© Copyright 2019-2022 ABB. All rights reserved.
6 Troubleshooting
6.2.5 Problem starting or connecting the FlexPendant