104 Parameters
173.06 Internal inverter
inhibitors 2
Indicates the internal conditions that are inhibiting the
inverter from connecting to grid.
0b0000/
Bit list
b0...b1: Reserved
b2: Open door
b3...b15: Reserved
173.07 Internal inverter
inhibitors 3
Indicates the internal conditions that are inhibiting the
inverter from connecting to grid.
0b0000/
Bit list
b0: Power module not
ready
b1: Low input voltage
b2: High input voltage
b3: Wake-up monitor
b4: Grounding
b5: Insulation resistance
b6: AC disconnection
device open
b7...b15: Reserved
173.11 Output power status Shows the status of power production. Disconnecte
d/ List
Disconnected Inverter is disconnected from the grid. 0
Starting Inverter is running start routines 1
MPP tracking Inverter is tracking MPP. 2
Minimum DC voltage MPPT is running against minimum DC voltage. 3
Maximum DC voltage MPPT is running against maximum DC voltage. 4
Active power limit Active power is limited. 5
Reactive power limit Reactive power is limited. 6
Both limits Both active and reactive powers are limited. 7
Power reference Inverter is in power reference mode (test mode). 8
User DC reference Inverter is in user reference mode (test mode). 9
Q compensation Inverter is in Q compensation mode. 10
173.12 Disconnect trigger Shows the reason for latest disconnection from grid. Connected/
List
Connected 0
Grid unstable 1
External command 2
Power too low 3
Too high DC voltage 4
Not enabled 5
Active fault 6
Other 7
No disconnection 8
173.20 Grid monitoring ready in Shows remaining time before connection is allowed by
grid monitoring.
-/ Real
0 … 10000 s Grid monitoring ready time. 1 = 1 s
No. Name/Value Description Def/
FbEq16/32