94 Parameters
150.47 FBA B Actual value 1 Shows raw (unmodified) actual value ACT1 sent by
fieldbus adapter B to the master (PLC) if debugging is
enabled by parameter 150.42 FBA B debug mode.
This parameter is read-only.
-/ Real
-2147483648...
2147483647
Fieldbus adapter B actual value 1. 1 = 1
150.48 FBA B Actual value 2 Shows raw (unmodified) actual value ACT2 sent by
fieldbus adapter B to the master (PLC) if debugging is
enabled by parameter 150.42 FBA B debug mode.
This parameter is read-only.
-/ Real
-2147483648...
2147483647
Fieldbus adapter B reference value 2. 1 = 1
150.51 FBA B Timelevel sel Selects communication speed.
In general, lower speeds reduce CPU load. The table
below shows the read/write intervals for cyclic and
acyclic data with each parameter setting.
*Cyclic data consists of fieldbus Control and Status
words, Ref1, Ref2, Act1 and Act2.
**Acyclic data consists of the parameter data mapped to
parameter groups 155 FBA B data in and 156 FBA B
data out.
Normal/ List
Monitoring Low speed. Optimized for PC tool communication and
monitoring usage.
0
Normal Normal speed. 1
Fast Fast speed. 2
151 FBA A settings
Fieldbus adapter A configuration.
Note: FBA A is reversed for internal communication. We
recommend not to modify these parameters.
151.01 FBA type Shows the type of connected fieldbus adapter module.
0 = Module is not found or is not properly connected, or
is disabled by parameter 150.01 FBA A Enable;
1 = FPBA; 32 = FCAN; 37 = FDNA; 128 = FENA-11/21;
132 = PROFINET IO; 135 = FECA; 136 = FEPL;
485 = FSCA; 62944 = FSEA.
None/ List
None Module is not found or is not properly connected, or is
disabled with parameter 150.01 FBA A Enable.
0
Profibus-DP 1
LonWorks 21
CANopen 32
DeviceNet 37
ControlNet 101
Ethernet 128
PROFInet IO 132
EtherCAT 135
ETH Pwrlink 136
No. Name/Value Description Def/
FbEq16/32
Selection Cyclic* Acyclic**
Monitoring 10 ms 10 ms
Normal 2 ms 10 ms
Fast 500 µs 2 ms
Very fast 250 µs 500 µs