Parameters 93
DC voltage
Reserved.
3
Active power 4
Reactive power 5
150.39 FBA B SW tr src Selects source of fieldbus status word when parameter
150.36 FBA B SW sel is set to Transparent.
Not selected/
List
Not selected No source selected. 0
Other See Terms and abbreviations on page 57.
150.40 FBA B act1 transparent
source
When parameter 150.37 FBA B act1 type is set to
Transparent mode, this parameter selects the type of
actual value 1 transmitted to the fieldbus network
through fieldbus adapter B.
Not selected/
List
Not selected No source selected. 0
Other See Terms and abbreviations on page 57.
150.41 FBA B act2 transparent
source
Selects type of actual value 2 transmitted to the fieldbus
network through fieldbus adapter B.
Not selected/
List
Not selected No source selected. 0
Other See Terms and abbreviations on page 57.
150.42 FBA B debug mode Enables the display of raw (unmodified) data received
from and sent to fieldbus adapter B in parameters
150.43…150.48.
This functionality should only be used for debugging.
Disabled/ List
Disabled Display of raw data from fieldbus adapter B disabled. 0
Fast Debug mode is enabled. Cyclical data update is as fast
as possible which increases the CPU load on the
inverter.
1
150.43 FBA B Control Word Shows raw (unmodified) control word sent by the master
(PLC) to fieldbus adapter B if debugging is enabled by
parameter 150.42 FBA B debug mode.
This parameter is read-only.
-/ Data
150.44 FBA B Reference REF1 Shows raw (unmodified) reference REF1 sent by the
master (PLC) to fieldbus adapter B if debugging is
enabled by parameter 150.42 FBA B debug mode.
This parameter is read-only.
-/ Real
-2147483648...
2147483647
Fieldbus adapter B reference value 1. 1 = 1
150.45 FBA B Reference REF2 Shows raw (unmodified) reference REF2 sent by the
master (PLC) to fieldbus adapter B if debugging is
enabled by parameter 150.42 FBA B debug mode.
This parameter is read-only.
-/ Real
-2147483648...
2147483647
Fieldbus adapter B reference value 2. 1 = 1
150.46 FBA B Status Word Shows raw (unmodified) status word sent by fieldbus
adapter B to the master (PLC) if debugging is enabled
by parameter 150.42 FBA B debug mode.
This parameter is read-only.
-/ Data
No. Name/Value Description Def/
FbEq16/32

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB PVS980-58 and is the answer not in the manual?

ABB PVS980-58 Specifications

General IconGeneral
BrandABB
ModelPVS980-58
CategoryInverter
LanguageEnglish

Related product manuals