92 Parameters
Warning Inverter generates only warning, no other actions are
taken due to comm loss.
3
150.33 FBA B comm loss t out Defines time delay before the action defined by
parameter 50.02 Comm loss func is taken. Time count
starts when the link fails to update the message.
0.3 s/ Real
0.3 … s Time delay. 10 = 1 s
150.34 FBA B ref1 type Selects type and scaling of reference 1 received from
fieldbus adapter B.
Voltage or
power/
List
Voltage or power Type and scaling is chosen automatically according to
the currently active operation mode.
0
Transparent No scaling is applied. 1
General Generic reference without a specific unit. 2
DC voltage
Reserved.
3
Active power 4
Reactive power 5
150.35 FBA B ref2 type Selects type and scaling of reference 2 received from
fieldbus adapter B.
Voltage or
power/
List
Voltage or power Type and scaling is chosen automatically according to
the currently active operation mode.
0
Transparent No scaling is applied. 1
General Generic reference without a specific unit. 2
DC voltage
Reserved.
3
Active power 4
Reactive power 5
150.36 FBA B SW sel Selects source of the Status word to be sent to the
fieldbus network through fieldbus adapter B.
Auto/ List
Auto Source of the Status word is chosen automatically. 0
Transparent mode Source selected by parameter 150.39 FBA B SW tr src
is transmitted as the Status word to the fieldbus network
through fieldbus adapter B.
1
150.37 FBA B act1 type Selects type and scaling of actual value 1 transmitted to
the fieldbus network through fieldbus adapter B.
Voltage or
power/
List
Voltage or power Type and scaling is chosen automatically according to
the currently active operation mode.
0
Transparent No scaling is applied. 1
General Generic reference without a specific unit. 2
DC voltage
Reserved.
3
Active power 4
Reactive power 5
150.38 FBA B act2 type Selects type and scaling of actual value 2 transmitted to
the fieldbus network through fieldbus adapter B.
Voltage or
power/
List
Voltage or power Type and scaling is chosen automatically according to
the currently active operation mode.
0
Transparent No scaling is applied. 1
General Generic reference without a specific unit. 2
No. Name/Value Description Def/