128 Parameters
189.07 SCADA shutdown Shows SCADA ramped shut down status. Inactive/ List
Inactive SCADA ramped shut down not active. 0
Active SCADA ramped shut down activated. 1
189.08 Shutdown event Sets event for ramped shut down. No action/
List
No action 0
Warning 1
Fault 2
Pure event 3
189.11 Reset active faults Resets active faults of the inverter. 0 / Real
0 … 1 1 = 1
190 Grid
measurements
Settings for grid voltage measurements of the inverter.
All parameters in this group are read-only, otherwise
noted.
190.01 Phase voltage U Shows rms value of phase voltage U. -/ Real
0.00 … 2000.00 V U phase voltage. 1 = 1 V/
100 = 1 V
190.02 Phase voltage V Shows rms value of phase voltage V. -/ Real
0.00 … 2000.00 V V phase voltage. 1 = 1 V/
100 = 1 V
190.03 Phase voltage W Shows rms value of phase voltage W. -/ Real
0.00 … 2000.00 V W phase voltage. 1 = 1 V/
100 = 1 V
190.04 Phase voltage max Shows maximum rms value of phase voltage. -/ Real
0.00 … 2000.00 V Maximum phase voltage. 1 = 1 V/
100 = 1 V
190.05 Phase voltage min Shows minimum rms value of phase voltage. -/ Real
0.00 … 2000.00 V Minimum phase voltage. 1 = 1 V/
100 = 1 V
190.06 Main voltage U-V Shows rms value of line-to-line voltage U-V. -/ Real
0.00 … 2000.00 V U-V line-to-line voltage. 1 = 1 V/
100 = 1 V
190.07 Main voltage V-W Shows rms value of line-to-line voltage V-W. -/ Real
0.00 … 2000.00 V V-W line-to-line voltage. 1 = 1 V/
100 = 1 V
190.08 Main voltage W-U Shows rms value of line-to-line voltage W-U. -/ Real
0.00 … 2000.00 V W-U line-to-line voltage. 1 = 1 V/
100 = 1 V
190.09 Main voltage max Shows maximum rms value of line-to-line voltages. -/ Real
0.00 … 2000.00 V Maximum line-to-line voltage. 1 = 1 V/
100 = 1 V
190.10 Main voltage min Shows minimum rms value of line-to-line voltages. -/ Real
0.00 … 2000.00 V Minimum line-to-line voltage. 1 = 1 V/
100 = 1 V
190.11 Phase voltage pos seq Shows positive sequence value of phase voltage. -/ Real
0.00 … 2000.00 V Positive sequence of phase voltage. 1 = 1 V/
100 = 1 V
No. Name/Value Description Def/
FbEq16/32