Parameters 151
213.18 Evening cool down
delay
Defines the time limit for which connecting the inverter is
not tried again after sleep mode is completed.
40 min/ Real
0 … 2000 min Time limit for cool down. 1 = 1 min
213.19 Fault time limit Defines the duration for which the wake-up state
machine stays in fault recovery mode, before moving
back to first start mode.
10 min/ Real
0 … 2000 min Time limit for cool down. 1 = 1 min
213.21 Min DC voltage for DC
contactors to stay
closed
Defines minimum DC voltage when DC contactors are
kept closed. The value is percent of peak value of the
grid’s phase-to-phase voltage.
102.0%/ Real
0.0 … 200.0% Percent of the diode rectified DC voltage. 10 = 1%
213.51 Night Q production Activates Night Q production mode. Disabled/ List
Disabled Night Q production mode disabled 0
Enabled Night Q production mode enabled 1
Force on Night Q production mode forced to On 3
213.52 Night Q low power Defines reactive power level required for the night Q
production to be active.
50 kVAr/
Real
0...1000 kVAr Night Q reactive power in kVAr. 1 = 1 kVAr
213.53 Night Q delay Defines time for which reactive power reference should
be below the low power limit for night Q production
mode to be deactivated.
10 s/ Real
0...3600 s Night Q reactive power delay time in seconds. 1 = 1 s
213.54 Night Q reference Defines reactive power reference for night Q production.
If value is set to 0 kVAr, the normal Qref is used.
0 kVAr/ Real
-4000... 4000 kVAr Night Q reactive power reference in kVAr. 1 = 1 kVAr
214 Switch control
Switch control parameters.
All parameters in this group are read-only unless
otherwise specified.
214.01 Feedback status Shows status of switch feedback signals. 0b0000/
Bit list
b0: AC contactor 1 AC contactor 1
b1: AC contactor 2 AC contactor 2
b2: AC contactor 3 AC contactor 3
b3: AC contactor 4 AC contactor 4
b4: DC contactor 1 DC contactor 1
b5: DC contactor 2 DC contactor 2
b6: DC contactor 3 DC contactor 3
b7: DC contactor 4 DC contactor 4
b8: AC breaker 1 AC breaker 1
b9: AC breaker 2 AC breaker 2
b10: AC breaker 3 AC breaker 3
b11: AC breaker 4 AC breaker 4
b12: DC switch 1 DC switch 1
b13: DC switch 2 DC switch 2
b14: DC switch 3 DC switch 3
b15: DC switch 4 DC switch 4
No. Name/Value Description Def/
FbEq16/32