150 Parameters
213.04 Max daily connect
attempts
Defines limit for daily connection attempts. When the
limit exceeds, a timer (parameter 213.15 Timeout for
exceeding daily connections) waits for multiple hours
before the next attempt.
10/ Real
0 … 20 Daily connection attempts limit. 1 = 1
213.05 Min input voltage for
wake-up
Defines minimum voltage for the wake-up of inverter.
The limit is set in percentage of the peak value of the
grid’s phase-to-phase voltage.
125.0%/ Real
0.0 … 200.0% Percent of peak value of the grid’s phase-to-phase
voltage.
10 = 1%
213.07 Delay for grid
connection
Defines time that the voltage is required to be between
the minimum voltage (parameter 213.05 Min input
voltage for wake-up) and the maximum voltage (1500 V)
for connecting to the DC input and grid.
5 min/ Real
0...100 min Connection voltage time limit. 1 = 1 min
213.08 Min input voltage for first
start
Defines minimum voltage for the first wake-up of
inverter. The value is a percent of the peak value of the
grid’s phase-to-phase voltage.
100.0%/ Real
0.0...200.0% Percent of peak value of the grid’s phase-to-phase
voltage.
10 = 1%
213.10 Delay for first start Defines the duration for which DC input voltage should
be between the limits of minimum voltage (parameter
213.08 Min input voltage for wake-up) and maximum
voltage (1500 V) for connecting the inverter to DC input
and grid for the first time.
0 min/ Real
0 … 2000 min Time limit for connecting the inverter. 1 = 1 min
213.11 Time for wake-up
completed
Defines the duration when the wake-up is considered to
be completed. After this timer the inverter starts
checking the sleep conditions.
60 min/ Real
0 … 2000 min Time for wake-up completed. 1 = 1 min
213.12 Min power for wake-up Defines minimum power level for the inverter to stay
connected to the grid during wakeup.
0.5%/ Real
0.0 … 100.0% Minimum power level for wake up. 10 = 1%
213.13 Disconnection delay in
wake-up
Defines the duration that the inverter stays connected to
the grid when produced power is less than the limit
defined in parameter 213.12 Min power for wake-up.
20 min/ Real
0 … 2000 min Time inverter stays connected to the grid. 1 = 1 min
213.14 Reconnection delay Defines delay time before a reconnection to the grid is
attempted again.
10 min/ Real
0 … 2000 min Delay time for reconnection. 1 = 1 min
213.15 Timeout for exceeding
daily connections
Defines delay time for new attempts of reconnection
after the limit (parameter 213.04 Max daily connect
attempts) is exceeded.
12 h/ Real
0 … 24 h Delay time for new attempts of reconnection. 1 = 1 h
213.16 Min power for sleep Defines minimum power level for disconnecting the
inverter in the evening.
0.5%/ Real
0 … 100% Percent of minimum power level for sleep. 1 = 1%
213.17 Disconnection delay for
sleep-mode
Defines the time limit for disconnection. The inverter
power is below the limit (213.16 Min power for sleep) for
this duration.
20 min/ Real
0 … 2000 min Time limit for disconnection. 1 = 1 min
No. Name/Value Description Def/
FbEq16/32