Parameters 101
Ref1 32bit Reference Ref1 (32 bits) 5
Ref2 32bit Reference Ref2 (32 bits) 6
Other See Terms and abbreviations on page 57. -
... ... ...
156.12 FBA B data out12 See parameter 156.01 FBA B data out1. None/ List
164 SCADA
configuration
SCADA configuration.
164.01 SCADA operation Enables SCADA input and output parameters or SCADA
monitoring only.
Disabled/ List
Disabled 0
Enabled 1
Monitoring only 2
164.02 SCADA profile Defines how SCADA input/output data is mapped to
SCADA parameters.
Profile 1/ List
Profile 1 PVS980-58 0
Profile 2 PVS800-57B 1
Profile 3 PVS980-58BC (energy storage) 2
Reserved - 3
164.04 Power scale SCADA scales active power limit according to this value. 2000.0 kW/
Real
0.0...5000.0 kW 10 = 1 kW
164.09 Fast Data-in sampling Selects sampling rate used in SCADA fast
communication.
-/ List
- 1 = 1
164.10 Heartbeat loss event Selects the event which is triggered when SCADA
heartbeat is lost.
Warning/ List
No action 0
Warning 1
Fault 2
Pure event 3
164.11 Comm hold-off after loss
event
Defines time for which SCADA communication stays in
hold-off state after communication has returned. During
timeout, the control commands are frozen. If value is
zero, the Timeout function is disabled.
120.00 s/
Real
0.00...3600.00 s 1 = 1 s
164.12 Heartbeat max interval Defines time in which heartbeat echo returns to the
interval. Otherwise communication is interpreted to be
lost.
5 s/ Real
1...600 s 1 = 1 s
164.13 Comm hold-off on boot
up
Defines the time in which watchdog is not monitoring the
link status, and when control commands from SCADA
are neglected in the boot up. This value is used to
prevent false alarms and control commands from
SCADA during the inverter start-up, when the
communication link is not yet established. If value is
zero, the feature is disabled.
60 s/ Real
0...600 s 1 = 1 s
No. Name/Value Description Def/
FbEq16/32