130 Parameters
196 System
Systems settings: Language selection, parameter save
and restore, control unit reboot.
196.01 Language Selects language of the parameter interface and other
displayed information.
Not selected/
List
Not selected Default value of the parameter and means that language
has not been selected.
0
English English (United States) 1
196.02 Passcode Pass codes can be entered into this parameter to
activate further access levels, for example additional
parameters, parameter lock, etc. See parameter 196.03
Access level status.
Entering “358” toggles the parameter lock, which
prevents the changing of all other parameters through
the control panel or the Drive composer PC tool.
-/ Real
196.03 Access level status Shows which access level is activated by pass codes
entered into parameter 196.02 Passcode.
This parameter is read-only.
0x0000/
Bit list
196.06 Param restore Restores original settings of the application, i.e.
parameter factory default values.
Note: This parameter cannot be changed while the
inverter is running.
Done/ List
Done Restoring is completed. 0
Restore defs All editable parameter values are restored to default
values, except
• I/O extension module settings
• control panel/PC communication settings
• fieldbus adapter settings
1
Clear all All editable parameter values are restored to default
values, except
• control panel/PC communication settings
• fieldbus adapter settings
PC tool communication is interrupted during the
restoring.
2
196.07 Param save Saves valid parameter values to the permanent
memory.
Note: A new parameter value is saved automatically
when changed from the PC tool or panel but not when
altered through a fieldbus connection.
Done/ List
Done Save completed. 0
Save Save in progress. 1
196.08 Control board boot Changing the value of this parameter to 1 reboots the
control unit. The value reverts to 0 automatically.
-/ Real
0 … 1 1 = Reboot control unit. 1 = 1
196.10 User set status Shows status of the user parameter sets.
This parameter is read-only.
n/a/ List
n/a No user parameter sets were saved. 0
Loading A user set is loaded. 1
Saving A user set is saved. 2
Faulted Invalid or empty parameter set. 3
User set 1 User set 1 is loaded. 4
No. Name/Value Description Def/
FbEq16/32