62 Parameters
101.14 Reactive power Calculated output reactive power. - / Real
-30000.00 …
30000.00 kVAr
Output reactive power. 1 = 1 kVAr/
100 = 1 kVAr
101.15 Reactive power % Calculated output reactive power in percentage of
nominal value.
- / Real
-1000.0 … 1000.0% Output reactive power in percentage of nominal value. 1 = 1%/
10 = 1%
101.16 CosPhi Calculated power factor (CosPhi). - / Real
-1.00 … 1.00 Power factor (CosPhi). 100 = 1
101.20 Converter current Measured line current. - / Real
0.00 … 30000.00 A Line current. 1 = 1 A/
100 = 1 A
101.21 Converter current% Measured line current in percentage of nominal value. - / Real
0.0 … 1000.0% Line current in percentage of nominal value. 1 = 1%/
10 = 1%
101.25 kWh to grid Counts the kWh generated from inverter into the grid. - / Real
0... 1000 kWh kWh generated from inverter into the grid. 1 = 1 kWh
101.26 MWh to grid Counts the MWh generated from inverter into the grid. - / Real
0... 1000 MWh MWh generated from inverter into the grid. 1 = 1 MWh
101.27 GWh to grid Counts the GWh generated from inverter into the grid. - / Real
0... 32767 GWh GWh generated from inverter into the grid. 1 = 1 GWh
101.64 Nominal power Nominal power of the inverter. - / Real
0 … 30000 kW Nominal power of the inverter. 1 = 1 kW
104 Warnings and
faults
Information on warnings and faults.
For description of individual warning and fault codes,
see chapter Troubleshooting on page 153.
All parameters in this group are read-only unless
otherwise noted.
104.01 Tripping fault Event code of the active fault. - /Data
104.02 Active fault 2 Event code of the second active fault. - /Data
104.03 Active fault 3 Event code of the third active fault. - /Data
104.04 Active fault 4 Event code of the fourth active fault. - /Data
104.05 Active fault 5 Event code of the fifth active fault. - /Data
104.06 Active warning 1 Event code of the active warning. - /Data
104.07 Active warning 2 Event code of the second active warning. - /Data
104.08 Active warning 3 Event code of the third active warning. - /Data
104.09 Active warning 4 Event code of the fourth active warning. - /Data
104.10 Active warning 5 Event code of the fifth active warning. - /Data
104.11 Latest fault Event code of the previously reset fault. - /Data
104.12 2nd latest fault Event code of the second previously reset fault. - /Data
104.13 3rd latest fault Event code of the third previously reset fault. - /Data
104.14 4th latest fault Event code of the fourth previously reset fault. - /Data
104.15 5th latest fault Event code of the fifth previously reset fault. - /Data
104.16 Latest warning Event code of the previously cleared warning. - /Data
104.17 2nd latest warning Event code of the second previously cleared warning. - /Data
104.18 3rd latest warning Event code of the third previously cleared warning. - /Data
No. Name/Value Description Def/