Parameters 97
Conf.err Adapter configuration error: The major or minor revision
code of the common program revision in the fieldbus
adapter module is not the revision required by the
module (see parameter 151.32 FBA comm SW ver) or
mapping file upload has failed more than three times.
3
Off-line Adapter is off-line. 4
On-line Adapter is on-line. 5
Reset Adapter is performing a hardware reset. 6
151.32 FBA comm SW ver Shows common program revision of the adapter module
in format axyz, where a = major revision number, xy =
minor revision number, z = correction number.
Example: 190A = revision 1.90A.
-/ Data
151.33 FBA appl SW ver Shows application program revision of the adapter
module in format axyz, where a = major revision
number, xy = minor revision number, z = correction
number or letter.
Example: 190A = revision 1.90A.
-/ Data
152 FBA A data in
Selection of data to be transferred from Inverter to
fieldbus controller through fieldbus adapter A.
Note: 32-bit values require two consecutive parameters.
Whenever a 32-bit value is selected in a data parameter,
the next parameter is automatically reserved.
152.01 FBA data in1 Parameters 152.01152.12 select data to be
transferred from the inverter to the fieldbus controller
through fieldbus adapter A.
None/ List
None None. 0
CW 16bit Virtual address for 16bit control word. 1
Ref1 16bit Virtual address for 16bit reference 1. 2
Ref2 16bit Virtual address for 16bit reference 2. 3
SW 16bit Virtual address for 16bit status word. 4
Act1 16bit Virtual address for 16bit actual value 1. 5
Act2 16bit Virtual address for 16bit actual value 2. 6
CW 32bit Virtual address for 32bit control word. 7
Ref1 32bit Virtual address for 32bit reference 1. 8
Ref2 32bit Virtual address for 32bit reference 2. 9
SW 32bit Virtual address for 32bit status word. 10
Act1 32bit Virtual address for 32bit actual value 1. 11
Act2 32bit Virtual address for 32bit actual value 2. 12
Other See Terms and abbreviations on page 57.
... ... ...
152.12 FBA data in12 See parameter 152.01 FBA data in1. None/ List
No. Name/Value Description Def/
FbEq16/32