30 Program features
cos phi (P) control curve
In cos phi (P) control curve mode, the reactive power generated by the inverter depends
on the active power. Grid voltage is used as a lock-in condition. When setting this curve,
crossing cos phi level one must be defined using two different points for the same point.
For example, input level 2 = 0,5; output level 2 = 1,0 and input level 3 = 0,5; output
level 3 = -1,0.
Figure 10. cos phi (P) control curve
cos phi (U) control curve
In cos phi (U) control curve mode, the reactive power generated by the inverter depends
on the grid voltage, as described in the example Q(U) control curve. The power reference
type is set in parameter124.06 Q power ref type = Q(x) regulation curve and
parameter124.30 Q(x) curve = CosPhi(U).
Figure 11. cos phi (U) control curve
cos phi
1
P
0,9
-0,9
0,6 0,7 0,8 0,9 1
0,2 0,3 0,4 0,5
124.33 Q(x) input level 1 = 0
124.35 Q(x) input level 3 = 0,5
124.36 Q(x) input level 4 = 1
124.37 Q(x) input level 5 = 1
124.38 Q(x) input level 6 = 1
124.34 Q(x) input level 2 = 0,5
124.39 Q(x) output level 1 = 1
124.40 Q(x) output level 2 = 1
124.41 Q(x) output level 3 = -1
124.42 Q(x) output level 4 = - 0,9
124.43 Q(x) output level 5 = - 0,9
124.44 Q(x) output level 6 = - 0,9
U
ac
[%]
124.39 Q(x) output level 1 = 0.95
124.40 Q(x) output level 2 = 0.95
124.44 Q(x) output level 6 = -0.95
124.33 Q(x) input
level 1 = 95%
124.34 Q(x) input
level 2 = 95%
124.35 Q(x) input level 3 = 100%
124.36 Q(x) input level 4 = 100%
124.37 Q(x) input level 5 = 105%
124.38 Q(x) input level 6 = 105%
cos phi
(cap)
cos phi
(ind)
124.43 Q(x) output level 5 = -0.95
124.41 Q(x) output level 3 = 1.00
124.42 Q(x) output level 4 = -1.00