Parameters 91
150.16 FBA A Status Word Shows status word sent by fieldbus adapter A to the
master (PLC).
This parameter is read-only.
-/ Data
150.17 FBA A Actual value 1 Shows raw actual value ACT1 sent by fieldbus adapter
A to the master (PLC).
This parameter is read-only.
-/ Real
-2147483648...
2147483647
Fieldbus adapter A actual value 1. 1 = 1
150.18 FBA A Actual value 2 Shows raw actual value ACT2 sent by fieldbus adapter
A to the master (PLC).
This parameter is read-only.
-/ Real
-2147483648...
2147483647
Fieldbus adapter A actual value 2. 1 = 1
150.21 FBA A Timelevel sel Selects communication speed.
In general, lower speeds reduce CPU load. The table
below shows the read/write intervals for cyclic and
acyclic data with each parameter setting.
*Cyclic data consists of fieldbus Control and Status
words, Ref1, Ref2, Act1 and Act2.
**Acyclic data consists of the parameter data mapped to
parameter groups 155 FBA B data in and 156 FBA B
data out.
Fast/ List
Monitoring Low speed. Optimized for PC tool communication and
monitoring usage.
0
Normal Normal speed. 1
Fast Fast speed. 2
150.31 FBA B Enable Enables communication between the inverter and
fieldbus adapter B, and specifies the slot the adapter is
installed into.
Disabled/ List
Disabled Communication between inverter and fieldbus adapter B
disabled.
0
Option slot 1 Communication between inverter and fieldbus adapter B
enabled. The adapter is in slot 1.
1
Option slot 2 Communication between inverter and fieldbus adapter B
enabled. The adapter is in slot 2.
2
Option slot 3 Communication between inverter and fieldbus adapter B
enabled. The adapter is in slot 3.
3
150.32 FBA B comm loss func Selects how the inverter reacts in a fieldbus
communication break. The time delay is defined by
parameter 50.03 Comm loss t out.
No action/
Real
No action Communication break does not cause any actions. 0
Fault Inverter trips on fault PANEL LOSS (FFFF) and the
inverter coasts to stop.
1
Fault always Inverter trips on fault and the inverter coasts to stop
always, when communication lost is noticed.
2
No. Name/Value Description Def/
FbEq16/32
Selection Cyclic* Acyclic**
Monitoring 10 ms 10 ms
Normal 2 ms 10 ms
Fast 500 µs 2 ms
Very fast 250 µs 2 µs