90 Parameters
Transparent No scaling is applied. 1
General Generic reference without a specific unit. 2
DC voltage
Reserved.
3
Active power 4
Reactive power 5
150.08 FBA A act2 type Selects type and scaling of actual value 2 transmitted to
the fieldbus network through fieldbus adapter A.
Voltage or
power/
List
Voltage or power Type and scaling is chosen automatically according to
the currently active operation mode.
0
Transparent No scaling is applied. 1
General Generic reference without a specific unit. 2
DC voltage
Reserved.
3
Active power 4
Reactive power 5
150.09 FBA A SW tr src Selects source for fieldbus status word when parameter
150.06 is set to Transparent mode.
Not selected/
List
Not selected No source selected. 0
Other See Terms and abbreviations on page 57.
150.10 FBA A act1 transparent
source
Selects source for fieldbus actual value 1 when
parameter 150.07 is set to Transparent mode.
Not selected/
List
Not selected No source selected. 0
Other See Terms and abbreviations on page 57.
150.11 FBA A act2 transparent
source
Selects source for fieldbus actual value 2 when
parameter 150.08 is set to Transparent mode.
Not selected/
List
Not selected No source selected. 0
Other See Terms and abbreviations on page 57.
150.12 FBA A debug mode Enables display of raw (unmodified) data received from
and sent to fieldbus adapter A in parameters
150.13…150.18.
This functionality should only be used for debugging.
Disabled/ List
Disabled Display of raw data from fieldbus adapter A disabled. 0
Fast Debug mode is enabled. Cyclical data update is as fast
as possible which increases the CPU load on the
inverter.
1
150.13 FBA A Control Word Shows control word sent by the master (PLC) to fieldbus
adapter A.
This parameter is read-only.
-/ Data
150.14 FBA A Reference REF1 Shows raw reference REF1 sent by the master (PLC) to
fieldbus adapter A.
This parameter is read-only.
-/ Real
-2147483648...
2147483647
Fieldbus adapter A reference value 1. 1 = 1
150.15 FBA A Reference REF2 Shows raw reference REF2 sent by the master (PLC) to
fieldbus adapter A.
This parameter is read-only.
-/ Real
-2147483648...
2147483647
Fieldbus adapter A reference value 2. 1 = 1
No. Name/Value Description Def/
FbEq16/32