Parameters 89
Option slot 2 Communication between inverter and fieldbus adapter A
enabled. The adapter is in slot 2.
2
Option slot 3 Communication between inverter and fieldbus adapter A
enabled. The adapter is in slot 3.
3
150.02 FBA A comm loss func Selects how the inverter should react when fieldbus
communication breaks. The time delay is defined by
parameter 150.03 FBA A comm loss t out.
No action/
List
No action Communication break does not cause any actions. 0
Fault Inverter trips on PANEL LOSS (FFFF) fault. The inverter
stops and disconnects from the grid.
1
Fault always When communication is lost, the inverter trips on fault
and coasts to stop always.
2
Warning Inverter generates only warning, no other actions are
taken due to comm loss.
3
150.03 FBA A comm loss t out Defines time delay before the action defined by
parameter 150.02 FBA A comm loss func is taken. Time
count starts when the communication link fails to update
the message.
0.3 s/ Real
0.3 … s Time delay. 10 = 1 s
150.04 FBA A ref1 type Selects type and scaling of reference 1 received from
fieldbus adapter A.
Voltage or
power/
List
Voltage or power Type and scaling is chosen automatically according to
the currently active operation mode.
0
Transparent No scaling is applied. 1
General Generic reference without a specific unit. 2
DC voltage
Reserved.
3
Active power 4
Reactive power 5
150.05 FBA A ref2 type Selects type and scaling of reference 2 received from
fieldbus adapter A.
Voltage or
power/
List
Voltage or power Type and scaling is chosen automatically according to
the currently active operation mode.
0
Transparent No scaling is applied. 1
General Generic reference without a specific unit. 2
DC voltage
Reserved.
3
Active power 4
Reactive power 5
150.06 FBA A SW sel Selects source of status word to be sent to the fieldbus
network through fieldbus adapter A.
Auto/ List
Auto Source of Status word is chosen automatically. 0
Transparent mode Source selected by parameter 150.09 FBA A SW tr src
is transmitted as Status word to the fieldbus network
through fieldbus adapter A.
1
150.07 FBA A act1 type Selects type and scaling of actual value 1 transmitted to
the fieldbus network through fieldbus adapter A.
Voltage or
power/
List
Voltage or power Type and scaling is chosen automatically according to
the currently active operation mode.
0
No. Name/Value Description Def/
FbEq16/32