Parameters 145
210.04 Ignore insulation
resistance
Ignores insulation resistance measurement before
grounding. This action allows grounding when the
insulation resistance is low, e.g., during high moisture
mornings.
In all cases, grounding is opened (removed), if there is a
high grounding voltage or current.
Disabled/ List
Disabled Ignore insulation resistance disabled. 0
Enabled Ignore insulation resistance enabled. 1
210.05 Ungrounded operation Enables ungrounded operation. Set this parameter if the
type of panel in use can function without grounding.
Note: Grounding is open (removed) when input voltage
is higher than the limit to allow insulation resistance
measurement.
Disabled/ List
Disabled Ungrounded operation disabled. 0
Enabled Ungrounded operation enabled. 1
210.06 Unground on fault Enables ungrounding function in the event of fault. Disabled /
List
Disabled Ungrounding on fault is disabled. 0
Enabled Ungrounding on fault is enabled. 1
210.07 Night grounding Enables night grounding function. Night grounding
means grounding is active while input voltage is low.
Note: Grounding is open (removed) when the input
voltage is higher than the limit to allow insulation
resistance measurement.
Disabled/ List
Disabled Night grounding is disabled. 0
Enabled Night grounding is enabled. 1
210.08 Wake-up voltage Defines wake-up voltage. 500 V/ Real
0...1000 V Wake-up volt.age 1 = 1 V
210.09 Night mode voltage Defines night mode voltage. 400 V/ Real
0...1000 V Night mode voltage. 1 = 1 V
210.12 Grounding circuit
voltage fail action
Selects how the inverter should react in the event of a
grounding circuit voltage failure.
Warning/ List
Warning Indicates 57606 Grounding circuit over voltage warning
code in the event of grounding circuit voltage failure.
0
Fault Triggers a 37126 Grounding circuit over voltage fault
code in the event of grounding circuit voltage failure.
1
210.14 Total grounding current Shows rms value of the grounding current.
This parameter is read-only.
-/ Real
0.000...10.000 A Total grounding current 1 = 1 A/
1000 = 1 A
210.15 Resistive grounding
current
Shows resistive grounding current.
This parameter is read-only.
-/ Real
-10.000...10.000 A Resistive grounding current 1 = 1 A/
1000 = 1 A
210.16 Grounding current fault
action
Selects how the inverter should react in the event of
residual current failure.
Warning/ List
No No action selected. 0
Warning Indicates 57605 Residual current warning code in the
event of residual current failure.
1
No. Name/Value Description Def/
FbEq16/32