178 Troubleshooting
58130
(0xe312)
Grid external monitor
trip
Grid external monitor trip. Inverter automatically starts
operation when normal
conditions are achieved.
58144
(0xe320)
Transfer trip Transfer trip command received. Remove command.
58145
(0xe321)
Shutdown Shut down command received
from digital input or SCADA.
Remove command.
58146
(0xe322)
DC current
measurement faulty
DC current measurement is found
faulty. Connection is lost or sensor
is broken.
This check is done when DC
contactors are open.
Check DC connections and
sensor. Aux. code shows which
module activated the warning.
For example, number 1 refers
to module 1.
58147
(0xe323)
SCADA
communication
timeout
SCADA communication timeout.
Communication is lost when
heartbeat was not returned by
SCADA in time defined in
specification.
Aux. code 4 indicates that
communication has returned but is
currently in timeout state.
Control commands are frozen
during timeout state. Timeout
length can be configured with
parameter 164.11 Comm hold-
off after loss event.
58148
(0xe324
SCADA
communication lost
SCADA communication is lost.
Communication is lost if heartbeat
echo is not received within defined
time (see aux. code 3).
-
Code in
Dec
(Hex)
Pure event Cause What to do