Function IEC 61850 IEC 60617 ANSI/C37.2-2008
Overexcitation protection OEPVPH1 U/f> (1) 24-1
OEPVPH2 U/f> (2) 24-2
Negative-sequence overcurrent protection
for machines
MNSPTOC1 I2>M (1) 46M-1
MNSPTOC2 I2>M (2) 46M-2
Loss of load supervision LOFLPTUC1 3I< (1) 37M-1
LOFLPTUC2 3I< (2) 37M-2
Motor load jam protection JAMPTOC1 Ist> (1) 51LR-1
JAMPTOC2 Ist> (2) 51LR-2
Motor start-up supervision STTPMSU1 Is2t n< (1) 66/51LRS
Phase reversal protection PREVPTOC1 I2>> (1) 46R
Thermal overload protection for motors MPTTR1 3Ith>M (1) 49M
Motor differential protection MPDIF1 3dl>M 87M
High-impedance differential protection for
phase A
HIAPDIF1 dHi_A>(1) 87A
High-impedance differential protection for
phase B
HIBPDIF1 dHi_B>(1) 87B
High-impedance differential protection for
phase C
HICPDIF1 dHi_C>(1) 87C
Circuit breaker failure protection CCBRBRF1 3I>/Io>BF (1) 50BF
Master trip TRPPTRC1 Master Trip (1) 86/94-1
TRPPTRC2 Master Trip (2) 86/94-2
TRPPTRC3 Master Trip (3) 86/94-3
TRPPTRC4 Master Trip (4) 86/94-4
TRPPTRC5 Master Trip (5) 86/94-5
Arc protection ARCSARC1 ARC (1) AFD-1
ARCSARC2 ARC (2) AFD-2
ARCSARC3 ARC (3) AFD-3
Table continues on next page
1MAC252756-MB B Section 1
Introduction
REM615 ANSI 13
Point List Manual