2.3.1.41 LD0.LOFLPTUC1 Loss of load supervision (1) – 37M-1
Table 44: LD0.LOFLPTUC1 Loss of load supervision (1) – 37M-1
BitA
RegA IEC 61850 name SA name Description Values
LD0.LOFLPTUC1
2912 182.00 .Str.general PICKUP Stage pickup 1=Pickup
2913 182.01 .mcd
2914 182.02 .Op.general TRIP Stage trip 1=Trip
2915 182.03 .mcd
2.3.1.42 LD0.LOFLPTUC2 Loss of load supervision (2) – 37M-2
Table 45: LD0.LOFLPTUC2 Loss of load supervision (2) – 37M-2
BitA RegA IEC 61850 name SA name Description Values
LD0.LOFLPTUC2
4048 253 .Str.general PICKUP Stage pickup 1=Pickup
4049 253.1 .mcd
4050 253.2 .Op.general TRIP Stage trip 1=Trip
4051 253.3 .mcd
2.3.1.43 LD0.MAPGAPC1 Multipurpose protection (1) – MAP-1
Table 46: LD0.MAPGAPC1 Multipurpose protection (1) – MAP-1
BitA
RegA IEC 61850 name SA name Description Values
LD0.MAPGAPC1
3056 191.00 .Op.general TRIP Stage trip 1 = Trip
3057 191.01 .mcd
3058 191.02 .Str.general PICKUP Stage pickup 1 = Pickup
3059 191.03 .mcd
Section 2 1MAC252756-MB B