Figure 55: Single-phase earth-fault of phase A
Figure 55 shows phasors in single-phase earth-fault, where the faulted phase is phase
A. The angle difference between the polarizing quantity U
BC
and operating quantity
I
A
is marked as ϕ. Note that the polarizing quantity is rotated with 90°. The
Characteristic angle is assumed to be 0°.
Figure 56 shows phasors in two-phase short circuit failure, where the fault is between
phase B and phase C. The angle difference between the polarizing quantity
and operating quantity
is marked as ϕ.
Figure 55 and Figure 56 are valid if the phase rotation is ABC.
1MRS757488 H Section 6
Commissioning
RIO600 97
Installation and Commissioning Manual