Table 132: LD0.RTDGGIO physical I/O values
Reg A Scale IEC 61850 name SA name Description Values
LD0.RTDGGIO1 16 Bit Signed Integer
64 Value reported with a scale
factor of "1" when channel
configured as dimensionless
and with a scale factor of "100"
when channel configured as
either mA or RTD
.AnIn1.mag.f
RTD 1-Channel 1 Input Value -40...200 [°C]/0.0...20.0
[mA]/-10000...10000
1)
65 .AnIn2.mag.f RTD 1-Channel 2 Input Value -40...200 [°C]/0.0...20.0
[mA]/-10000...10000
1)
66 .AnIn3.mag.f RTD 1-Channel 3 Input Value -40...200 [°C]/0.0...20.0
[mA]/-10000...10000
1)
67 .AnIn4.mag.f RTD 1-Channel 4 Input Value -40...200 [°C]/0.0...20.0
[mA]/-10000...10000
1)
68 <reserved> <reserved> 0
69 <reserved> <reserved> 0
70 <reserved> <reserved> 0
71 <reserved> <reserved> 0
72 .AnIn1.range/.An
In2.range
RTD 1-Channel Range Information
Channel - 2 (High Byte)
Channel - 1 (Low Byte)
Normal – 0;
High – 1;
Low – 2;
High High – 3;
Low Low – 4;
73
.AnIn3.range/.An
In4.range
RTD 1-Channel Range Information
Channel - 4 (High Byte)
Channel - 3 (Low Byte)
Normal – 0;
High – 1;
Low – 2;
High High – 3;
Low Low – 4;
74
<reserved> <reserved> 0
75 <reserved> <reserved> 0
76 <reserved> <reserved> 0
77 <reserved> <reserved> 0
78 <reserved> <reserved> 0
79 <reserved> <reserved> 0
LD0.RTDGGIO2
80 Value reported with a scale
factor of "1" when channel
configured as dimensionless
and with a scale factor of "100"
when channel configured as
either mA or RTD
.AnIn1.mag.f
RTD 2-Channel 1 Input Value -40...200 [°C]/0.0...20.0
[mA]/-10000...10000
1)
81 .AnIn2.mag.f RTD 2-Channel 2 Input Value -40...200 [°C]/0.0...20.0
[mA]/-10000...10000
1)
82 .AnIn3.mag.f RTD 2-Channel 3 Input Value -40...200 [°C]/0.0...20.0
[mA]/-10000...10000
1)
83 .AnIn4.mag.f RTD 2-Channel 4 Input Value -40...200 [°C]/0.0...20.0
[mA]/-10000...10000
1)
84 <reserved> <reserved> 0
85 <reserved> <reserved> 0
86 <reserved> <reserved> 0
87 <reserved> <reserved> 0
Table continues on next page
Section 7 1MRS757488 H
Modbus TCP communication
196 RIO600
Installation and Commissioning Manual