Reg A Scale IEC 61850 name SA name Description Values
137 .AnIn3.range/.An
In4.range
RTD 5- Channel Range Information
Channel - 4 (High Byte)
Channel - 3 (Low Byte)
Normal – 0;
High – 1;
Low – 2;
High High – 3;
Low Low – 4;
138
<reserved> <reserved> 0
139 <reserved> <reserved> 0
140 <reserved> <reserved> 0
141 <reserved> <reserved> 0
142 <reserved> <reserved> 0
143 <reserved> <reserved> 0
LD0.RTDGGIO6
144 Value reported with a scale
factor of "1" when channel
configured as dimensionless
and with a scale factor of "100"
when channel configured as
either mA or RTD
.AnIn1.mag.f
RTD 6-Channel 1 Input Value -40...200 [°C]/0.0...20.0
[mA]/-10000...10000
1)
145 .AnIn2.mag.f RTD 6-Channel 2 Input Value -40...200 [°C]/0.0...20.0
[mA]/-10000...10000
1)
146 .AnIn3.mag.f RTD 6-Channel 3 Input Value -40...200 [°C]/0.0...20.0
[mA]/-10000...10000
1)
147 .AnIn4.mag.f RTD 6-Channel 4 Input Value -40...200 [°C]/0.0...20.0
[mA]/-10000...10000
1)
148 <reserved> <reserved> 0
149 <reserved> <reserved> 0
150 <reserved> <reserved> 0
151 <reserved> <reserved> 0
152 .AnIn1.range/.An
In2.range
RTD 6- Channel Range Information
Channel - 2 (High Byte)
Channel - 1 (Low Byte)
Normal – 0;
High – 1;
Low – 2;
High High – 3;
Low Low – 4;
153
.AnIn3.range/.An
In4.range
RTD 6- Channel Range Information
Channel - 4 (High Byte)
Channel - 3 (Low Byte)
Normal – 0;
High – 1;
Low – 2;
High High – 3;
Low Low – 4;
154
<reserved> <reserved> 0
155 <reserved> <reserved> 0
156 <reserved> <reserved> 0
157 <reserved> <reserved> 0
158 <reserved> <reserved> 0
159 <reserved> <reserved> 0
LD0.RTDGGIO7
Table continues on next page
1MRS757488 H Section 7
Modbus TCP communication
RIO600 199