Reg A Scale IEC 61850 name SA name Description Values
160 Value reported with a scale
factor of "1" when channel
configured as dimensionless
and with a scale factor of "100"
when channel configured as
either mA or RTD
.AnIn1.mag.f
RTD 7-Channel 1 Input Value -40...200 [°C]/0.0...20.0
[mA]/-10000...10000
1)
161 .AnIn2.mag.f RTD 7-Channel 2 Input Value -40...200 [°C]/0.0...20.0
[mA]/-10000...10000
1)
162 .AnIn3.mag.f RTD 7-Channel 3 Input Value -40...200 [°C]/0.0...20.0
[mA]/-10000...10000
1)
163 .AnIn4.mag.f RTD 7-Channel 4 Input Value -40...200 [°C]/0.0...20.0
[mA]/-10000...10000
1)
164 <reserved> <reserved> 0
165 <reserved> <reserved> 0
166 <reserved> <reserved> 0
167 <reserved> <reserved> 0
168 .AnIn1.range/.An
In2.range
RTD 7- Channel Range Information
Channel - 2 (High Byte)
Channel - 1 (Low Byte)
Normal – 0;
High – 1;
Low – 2;
High High – 3;
Low Low – 4;
169
.AnIn3.range/.An
In4.range
RTD 7- Channel Range Information
Channel - 4 (High Byte)
Channel - 3 (Low Byte)
Normal – 0;
High – 1;
Low – 2;
High High – 3;
Low Low – 4;
170
<reserved> <reserved> 0
171 <reserved> <reserved> 0
172 <reserved> <reserved> 0
173 <reserved> <reserved> 0
174 <reserved> <reserved> 0
175 <reserved> <reserved> 0
LD0.RTDGGIO8
176 Value reported with a scale
factor of "1" when channel
configured as dimensionless
and with a scale factor of "100"
when channel configured as
either mA or RTD
.AnIn1.mag.f
RTD 8-Channel 1 Input Value -40...200 [°C]/0.0...20.0
[mA]/-10000...10000
1)
177 .AnIn2.mag.f RTD 8-Channel 2 Input Value -40...200 [°C]/0.0...20.0
[mA]/-10000...10000
1)
178 .AnIn3.mag.f RTD 8-Channel 3 Input Value -40...200 [°C]/0.0...20.0
[mA]/-10000...10000
1)
179 .AnIn4.mag.f RTD 8-Channel 4 Input Value -40...200 [°C]/0.0...20.0
[mA]/-10000...10000
1)
180 <reserved> <reserved> 0
181 <reserved> <reserved> 0
182 <reserved> <reserved> 0
183 <reserved> <reserved> 0
184 .AnIn1.range/.An
In2.range
RTD 8- Channel Range Information
Channel - 2 (High Byte)
Channel - 1 (Low Byte)
Normal – 0;
High – 1;
Low – 2;
High High – 3;
Low Low – 4;
Table continues on next page
Section 7 1MRS757488 H
Modbus TCP communication
200 RIO600
Installation and Commissioning Manual