Bit A Reg A IEC 61850 name SA name Description Values
1)
1. LD0.SCMLGGIO8/
LD0.SCMHGGIO8
2. LD0.SCMLPGGIO8/
LD0.SCMHPGGIO8
3. LD0.SCMLDGGIO8/
LD0.SCMHDGGIO8
4. LD0.SCMLEGGIO8/
LD0.SCMHEGGIO8
5. LD0.SCMLCGGIO8/
LD0.SCMHCGGIO8
6. LD0.TCSLSCBR8/
LD0.TCSHSCBR8
SCM-8
1888 1530 .Ind1.stVal Digital Input Channel 1 0/1 = Off/On
1889 1530.01 .Ind2.stVal Digital Input Channel 2 0/1 = Off/On
1890 1530.02 .Ind3.stVal Digital Input Channel 3 0/1 = Off/On
1891 1530.03 .Ind4.stVal Digital Input Channel 4 0/1 = Off/On
1892 1530.04 RELEASE_ES Release Earth Switch
Information
0/1 = Off/On
1893 1530.05 RELEASE_DS Release Disconnector
Information
0/1 = Off/On
1894 1530.06 REED_ES REED Earth Switch
Information
0/1 = Off/On
1895 1530.07 RELEASE_CB Release Circuit Breaker
Information
0/1 = Off/On
1896 1530.08 .Ind10.stVal Error Code: No Fault 0/1 = Off/On
1897 1530.09 .Ind11.stVal Error Code: Device Error 0/1 = Off/On
1898 1530.1 .Ind12.stVal Error code: Release 0/1 = Off/On
1899 1530.11 .Ind13.stVal Error Code: No Act 0/1 = Off/On
1900 1530.12 .Ind14.stVal Error Code: Interlocking Error 0/1 = Off/On
1901 1530.13 .Ind15.stVal Error Code: REED/ Release
Error
0/1 = Off/On
1902 1530.14 .Ind16.stVal Error Code: Position Error 0/1 = Off/On
1903 1530.15 .Ind17.stVal Error Code: Time-out Error 0/1 = Off/On
1904 1531 .CircAlm.stVal Trip Circuit Supervision Alarm
Status
0/1 = Off/On
1905 1531.01 .CircAlm.stVal Trip Circuit Supervision Alarm
Status
0/1 = Off/On
1)
1. LD0.SCMLGGIO9/
LD0.SCMHGGIO9
2. LD0.SCMLPGGIO9/
LD0.SCMHPGGIO9
3. LD0.SCMLDGGIO9/
LD0.SCMHDGGIO9
4. LD0.SCMLEGGIO9/
LD0.SCMHEGGIO9
5. LD0.SCMLCGGIO9/
LD0.SCMHCGGIO9
6. LD0.TCSLSCBR9/
LD0.TCSHSCBR9
SCM-9
Table continues on next page
Section 7 1MRS757488 H
Modbus TCP communication
248 RIO600
Installation and Commissioning Manual