Bit A Reg A IEC 61850 name SA name Description Values
1920 1532 .Ind1.stVal Digital Input Channel 1 0/1 = Off/On
1921 1532.01 .Ind2.stVal Digital Input Channel 2 0/1 = Off/On
1922 1532.02 .Ind3.stVal Digital Input Channel 3 0/1 = Off/On
1923 1532.03 .Ind4.stVal Digital Input Channel 4 0/1 = Off/On
1924 1532.04 RELEASE_ES Release Earth Switch
Information
0/1 = Off/On
1925 1532.05 RELEASE_DS Release Disconnector
Information
0/1 = Off/On
1926 1532.06 REED_ES REED Earth Switch
Information
0/1 = Off/On
1927 1532.07 RELEASE_CB Release Circuit Breaker
Information
0/1 = Off/On
1928 1532.08 .Ind10.stVal Error Code: No Fault 0/1 = Off/On
1929 1532.09 .Ind11.stVal Error Code: Device Error 0/1 = Off/On
1930 1532.1 .Ind12.stVal Error code: Release 0/1 = Off/On
1931 1532.11 .Ind13.stVal Error Code: No Act 0/1 = Off/On
1932 1532.12 .Ind14.stVal Error Code: Interlocking Error 0/1 = Off/On
1933 1532.13 .Ind15.stVal Error Code: REED/ Release
Error
0/1 = Off/On
1934 1532.14 .Ind16.stVal Error Code: Position Error 0/1 = Off/On
1935 1532.15 .Ind17.stVal Error Code: Time-out Error 0/1 = Off/On
1936 1533 .CircAlm.stVal Trip Circuit Supervision Alarm
Status
0/1 = Off/On
1937 1533.01 .CircAlm.stVal Trip Circuit Supervision Alarm
Status
0/1 = Off/On
1)
1. LD0.SCMLGGIO10/
LD0.SCMHGGIO10
2. LD0.SCMLPGGIO10/
LD0.SCMHPGGIO10
3. LD0.SCMLDGGIO10/
LD0.SCMHDGGIO10
4. LD0.SCMLEGGIO10/
LD0.SCMHEGGIO10
5. LD0.SCMLCGGIO10/
LD0.SCMHCGGIO10
6. LD0.TCSLSCBR10/
LD0.TCSHSCBR10
SCM-10
1952 1534 .Ind1.stVal Digital Input Channel 1 0/1 = Off/On
1953 1534.01 .Ind2.stVal Digital Input Channel 2 0/1 = Off/On
1954 1534.02 .Ind3.stVal Digital Input Channel 3 0/1 = Off/On
1955 1534.03 .Ind4.stVal Digital Input Channel 4 0/1 = Off/On
1956 1534.04 RELEASE_ES Release Earth Switch
Information
0/1 = Off/On
1957 1534.05 RELEASE_DS Release Disconnector
Information
0/1 = Off/On
1958 1534.06 REED_ES REED Earth Switch
Information
0/1 = Off/On
Table continues on next page
1MRS757488 H Section 7
Modbus TCP communication
RIO600 249