Bit A Reg A IEC 61850 name SA name Description Values
1959 1534.07 RELEASE_CB Release Circuit Breaker
Information
0/1 = Off/On
1960 1534.08 .Ind10.stVal Error Code: No Fault 0/1 = Off/On
1961 1534.09 .Ind11.stVal Error Code: Device Error 0/1 = Off/On
1962 1534.1 .Ind12.stVal Error code: Release 0/1 = Off/On
1963 1534.11 .Ind13.stVal Error Code: No Act 0/1 = Off/On
1964 1534.12 .Ind14.stVal Error Code: Interlocking Error 0/1 = Off/On
1965 1534.13 .Ind15.stVal Error Code: REED/ Release
Error
0/1 = Off/On
1966 1534.14 .Ind16.stVal Error Code: Position Error 0/1 = Off/On
1967 1534.15 .Ind17.stVal Error Code: Time-out Error 0/1 = Off/On
1968 1535 .CircAlm.stVal Trip Circuit Supervision Alarm
Status
0/1 = Off/On
1969 1535.01 .CircAlm.stVal Trip Circuit Supervision Alarm
Status
0/1 = Off/On
1) Applicable (read only) data attributes are mentioned under their respective data objects.
LD0.SCMLGGIO/LD0.SCMHGGIO
- .Ind1.stVal
- .Ind2.stVal
- .Ind3.stVal
- .Ind4.stVal
LD0.SCMLPGGIO/LD0.SCMHPGGIO
- .Ind1.stVal
- .Ind2.stVal
- .Ind3.stVal
- .Ind4.stVal
- RELEASE_ES
- RELEASE_DS
- REED_ES
- .Ind10.stVal
- .Ind11.stVal
- .Ind12.stVal
- .Ind13.stVal
- .Ind14.stVal
- .Ind15.stVal
- .Ind16.stVal
- .Ind17.stVal
LD0.SCMLDGGIO/LD0.SCMHDGGIO
- .Ind1.stVal
- .Ind2.stVal
- .Ind3.stVal
- .Ind4.stVal
- RELEASE_DS
- .Ind10.stVal
- .Ind11.stVal
- .Ind12.stVal
- .Ind13.stVal
- .Ind14.stVal
- .Ind16.stVal
- .Ind17.stVal
LD0.SCMLEGGIO/LD0.SCMHEGGIO
- .Ind1.stVal
- .Ind2.stVal
- .Ind3.stVal
- .Ind4.stVal
- RELEASE_ES
- REED_ES
- .Ind10.stVal
- .Ind11.stVal
Section 7 1MRS757488 H