EasyManua.ls Logo

ABB Remote I/O RIO600 - Table 207: Electromagnetic compatibility and immunity tests

ABB Remote I/O RIO600
312 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Table 205: Contact tests
Description Type test value Reference
Make and carry Signaling contacts
5 A, continuous
10 A for 3 s
15 A for 0.5 s
IEC 60255-1, IEC 61810-1 and
IEEE C37.90-2005
Breaking capacity for DC, L/R
≤40 ms
Signaling contacts
48 V, 1.00 A
110 V, 0.25 A
220 V, 0.15 A
IEC 60255-1, IEC 61810-1 and
IEEE C37.90-2005
Mechanical durability 10000 operations IEC 60255-1, IEC 61810-1 and
IEEE C37.90-2005
Table 206: Insulation tests
Description
1)
Type test value Reference
Dielectric tests 2 kV, 50 Hz, 1 min
500 V, 50 Hz, 1 min for
communication
2.8 kV DC, 1 min
700 V DC, 1 min for
communication
IEC 60255-27 and IEEE
C37.90-2005
Impulse voltage tests 5 kV, 1.2/50 μs, 0.5 J IEC 60255-27 and IEEE
C37.90-2005
Insulation resistance
measurements
>100 MΩ, 500 V DC IEC 60255-27
1) Insulation tests are not applicable to SIM8F/SIM4F
Table 207: Electromagnetic compatibility and immunity tests
Description
Type test value Reference
Electrostatic discharge IEC 60255-26 and IEC
61000-4-2, Level 3
Air discharge 8 kV
Radio frequency
electromagnetic field (amplitude
modulated)
10 V/m (RMS)
f = 80...1000 MHz and 1.4...2.7
GHz
IEC 60255-26 and IEC
61000-4-3, Level 3
Radio frequency
electromagnetic field from digital
radio telephones (pulse
modulated)
10 V/m (RMS)
f = 900 MHz, 1890 MHz
IEC 61000-4-3, Level 3
Power frequency (50 Hz)
magnetic field
IEC 60255-26 and IEC
61000-4-8
Continuous 100 A (RMS)/m
3 s 300 A (RMS)/m
Table continues on next page
Section 11 1MRS757488 H
Device and functionality tests
294 RIO600
Installation and Commissioning Manual

Table of Contents

Related product manuals