EasyManua.ls Logo

ABB Remote I/O RIO600 - Page 303

ABB Remote I/O RIO600
312 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Description Type test value Reference
Pulsed magnetic field 1000 A/m; 6.4/16 μs Tr/Td; 5
pulses positive/negative; 10 s
(time interval)
IEC 61000-4-9, Level 5
Conducted disturbance induced
by radio frequency fields,
Amplitude modulated
0.15...80 MHz - 10 V (unmod,
RMS); 80% AM (1 kHz); 150 Ω
source impedance
27 and 68 MHz (spot
frequencies); 10 V (unmod,
RMS); 80% AM (1 kHz); 150 Ω
source impedance
IEC 60255-26 and IEC
61000-4-6, Level 3
Fast low-energy transient (EFT)
(including functional earth port)
5/50 ns Tr/Td; 5 kHz repetition
frequency
4 kV (peak) for power supply
input/output ports and 2 kV
(peak) for communication port
IEC 60255-26 and IEC
61000-4-4
Damped oscillatory waves
(HFD) 100 kHz and 1 MHz burst
100 kHz and 1 MHz frequency;
75 ns Tr; 40 Hz and 400 Hz
repetition frequency; 200 Ω
source impedance
IEC 60255-26 and IEC
61000-4-18
Power supply and input/
output ports
Differential mode: 1 kV (peak)
Common mode: 2.5 kV (peak)
Communication port Differential mode: not applicable
Common mode: 1 kV (peak)
Slow high-energy transient
(surge1.2/50 μs voltage pulse)
1.2/50 μs Tr/Th (open circuit)
8/20 μs Tr/Th (short circuit)
IEC 60255-26 and IEC
61000-4-5
Auxiliary power supply and
input/output ports
1)
±4 kVp (L-Gnd) ±2 kVp (L-L)
Communication port ±2 kVp (L-Gnd) while no L-L test
is applicable
Voltage dips, short interruptions
and voltage variation immunity
tests (AC 50 Hz and 60 Hz)
30% reduction for 25/30 cycles
60% reduction for 10/12 cycles
100% reduction for 0.5, 1.0, 2.5
and 5.0 cycles
100% reduction for 250/300
cycles
IEC 60255-26 and IEC
61000-4-11
Voltage dips, supply interruption
and voltage variations on DC
input power port (immunity
tests)
30% reduction for 500 ms
60% reduction for 200 ms
100% reduction for 10, 20, 30
and 50 ms
100% reduction for 5 s
IEC 60255-26 and IEC
61000-4-29
Ripple voltage 15% U
n
frequencies of ripple
100/120 Hz (for 50/60 Hz)
IEC 60255-26, IEC 61000-4-17
and IEEE C37.90-2005
Gradual shut-down/start-up test
(for DC power supply)
IEC 60255-26
Ramp towards shut-down 60 s
Wait at power of condition 5 min
Ramp towards start-up 60 s
Power frequency voltage 50 Hz
and 60 Hz
Input/output port
IEC 60255-26 and IEC
61000-4-16
Table continues on next page
1MRS757488 H Section 11
Device and functionality tests
RIO600 295
Installation and Commissioning Manual

Table of Contents