Description Type test value Reference
Differential mode 150 V (RMS)
100 Ω coupling resistor
0.1 μF coupling capacitor
Common mode 300 V (RMS)
220 Ω coupling resistor
0.47 μF coupling capacitor
Emission tests IEC 60255-26
Radiated
30...230 MHz <40 dB (μV/m) quasi-peak,
measured at 10 m distance
230...1000 MHz <47 dB (μV/m) quasi-peak,
measured at 10 m distance
Conducted
0.15...0.50 MHz <79 dB (μV) quasi-peak
<66 dB (μV) average
0.5...30 MHz <73 dB (μV) quasi-peak
<60 dB (μV) average
1) When SCM is configured as a generic I/O, the level supported is ±2 kVp (L-Gnd) ±1 kVp (L-L)
Table 208: Electromagnetic compatibility and immunity tests according to ANSI standards
Description
Type test value Reference
1 MHz oscillatory SWC test All ports:
±2.5 kV common mode/
differential mode
IEEE C37.90.1-2002
Fast transient SWC test All ports:
±4 kV common mode/differential
mode
IEEE C37.90.1-2002
Radio frequency interference
tests
20 V/m (prior to modulation)
f = 80...1000 MHz (AM)
f = 900 MHz (PM)
IEEE C37.90.2-2004
Electrostatic discharge test ±15 kV air discharge IEEE C37.90.3-2001
Table 209: Mechanical tests
Description
Type test value Reference
Vibration tests (sinusoidal) Class 1 IEC 60255-21-1
Vibration response test f = 10…150 Hz
Peak acceleration: 0.5 g
1 sweep cycle in each axis
Vibration endurance test f = 10…150 Hz
Peak acceleration: 1.0 g
20 sweep cycles in each axis
Shock and bump test Class 1 IEC 60255-21-2
Shock response test Peak acceleration: 5 g
Duration of the pulse: 11 ms
Number of pulses in each
direction: 3
Table continues on next page
Section 11 1MRS757488 H
Device and functionality tests
296 RIO600
Installation and Commissioning Manual