EasyManua.ls Logo

ABB RET670 - Page 157

ABB RET670
888 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Basic data:
Cable loop
resistance:
<100 ft AWG10 (one way between the junction point and the farthest
CT) gives loop resistance 2 · 0.05 = 0.1 Ohms
Note! Only one way as the system grounding is limiting the ground-
fault current. If high ground-fault current exists use two way cable.
Max fault current: The maximum through fault current given by the transformer
reactance for example, 28 kA.
Calculation:
28000
(0.5 0.1) 42
400
VR V> × + =
EQUATION1766-ANSI V1 EN (Equation 42)
Select a setting of
TripPickup
=60 V.
The current transformer knee point voltage can roughly be calculated from the rated values, considering
knee point voltage to be about 70% of the accuracy limit voltage.
(4 0.5) 100 0.7 315VkneeANSI V> + × × =
EQUATION1767-ANSI V1 EN (Equation 43)
that is, greater than 2 ·
TripPickup
.
Check from the table of selected resistances the required series stabilizing resistor
value to use. Since this application it is not required to be so sensitive, select R
series=150 ohm, which gives an IED current of 400 mA.
To calculate the sensitivity at operating voltage, refer to equation 44 which gives an
acceptable value; in fact in this example the sensitivity is about 13% of the nominal
current of the CT:
( )
2000
400 0 60 .140
5
IP approx A= × ° + £
EQUATION1886-ANSI V1 EN (Equation 44)
Where
IR= 100mA is the current drawn by the IED circuit
I
mag
= 15mA is the magnetizing current of the CT at the operating voltage
TripPickup
Ires = 5 mA is the current drawn by the non-linear resistor at the operating voltage
TripPickup
1MRK504116-UUS C Section 3
IED application
151
Application manual

Table of Contents

Other manuals for ABB RET670

Related product manuals