EasyManua.ls Logo

ABB RET670 - Page 202

ABB RET670
888 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Parallel line applications
This type of networks are defined as those networks where the parallel transmission
lines terminate at common nodes at both ends. We consider the three most common
operation modes:
parallel line in service
parallel line out of service and grounded
parallel line out of service and not grounded
Parallel line in service
This type of application is very common and applies to all normal sub-transmission
and transmission networks.
Here is the description of what happens when a fault occurs on the parallel line, as
shown in figure 64.
From symmetrical components, it is possible to derive the impedance Z at the IED
point for normal lines without mutual coupling according to equation
104.
ph ph
0 1 ph 0 N
ph 0
1
V V
Z Z I 3I K
I 3I
3 Z
Z = =
- + ×
+ ×
×
EQUATION1275 V2 EN (Equation 104)
Where:
Vph is phase-to-ground voltage at the IED point
Iph is phase current in the faulty phase
3I0 is ground-fault current
Z1 is positive sequence impedance
Z0 is zero sequence impedance
Section 3 1MRK504116-UUS C
IED application
196
Application manual

Table of Contents

Other manuals for ABB RET670

Related product manuals