EasyManua.ls Logo

ABB RET670 - Page 250

ABB RET670
888 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Check the reduction of a reach for the overreaching zones due to the effect of the zero
sequence mutual coupling. The reach is reduced for a factor:
0
0 1
2 1 0
m
f
Z
K
Z Z R
= -
× + +
EQUATION1426 V1 EN (Equation 155)
If the denominator in equation 155 is called B and Z0m is simplified to X0m, then the
real and imaginary part of the reach reduction factor for the overreaching zones can be
written as:
( )
( )
( ) ( )
2 2
0 Re
Re 0 1
Re Im
X m B
K
B B
×
= -
+
EQUATION1427 V2 EN (Equation 156)
( )
( )
( ) ( )
2 2
0 Im
Im 0
Re Im
X m B
K
B B
×
=
+
EQUATION1428 V2 EN (Equation 157)
Parallel line is out of service and grounded in both ends
Apply the same measures as in the case with a single set of setting parameters. This
means that an underreaching zone must not overreach the end of a protected circuit for
the single phase-to-ground-faults. Set the values of the corresponding zone (zero-
sequence resistance and reactance) equal to:
R
0E
R
0
1
X
m0
2
R
0
2
X
0
2
+
--------------------------
+
è ø
ç ÷
æ ö
×=
EQUATION561 V1 EN
(Equation 158)
X
0E
X
0
1
X
m0
2
R
0
2
X
0
2
+
--------------------------
è ø
ç ÷
æ ö
×=
EQUATION562 V1 EN (Equation 159)
Setting of reach in resistive direction
Set the resistive reach independently for each zone, and separately for phase-to-phase
(R1PP), and phase-to-ground loop (R1PG) measurement.
Set separately the expected fault resistance for phase-to-phase faults (R1PP) and for
the phase-to-ground faults (RFPG) for each zone. Set all remaining reach setting
parameters independently of each other for each distance zone.
Section 3 1MRK504116-UUS C
IED application
244
Application manual

Table of Contents

Other manuals for ABB RET670

Related product manuals