Check the reduction of a reach for the overreaching zones due to the effect of the zero
sequence mutual coupling. The reach is reduced for a factor:
0
0 1
2 1 0
m
f
Z
K
Z Z R
= -
× + +
EQUATION1426 V1 EN (Equation 155)
If the denominator in equation 155 is called B and Z0m is simplified to X0m, then the
real and imaginary part of the reach reduction factor for the overreaching zones can be
written as:
( )
( )
( ) ( )
2 2
0 Re
Re 0 1
Re Im
X m B
K
B B
×
= -
+
EQUATION1427 V2 EN (Equation 156)
( )
( )
( ) ( )
2 2
0 Im
Im 0
Re Im
X m B
K
B B
×
=
+
EQUATION1428 V2 EN (Equation 157)
Parallel line is out of service and grounded in both ends
Apply the same measures as in the case with a single set of setting parameters. This
means that an underreaching zone must not overreach the end of a protected circuit for
the single phase-to-ground-faults. Set the values of the corresponding zone (zero-
sequence resistance and reactance) equal to:
R
0E
R
0
1
X
m0
2
R
0
2
X
0
2
+
--------------------------
+
è ø
ç ÷
æ ö
×=
EQUATION561 V1 EN
(Equation 158)
X
0E
X
0
1
X
m0
2
R
0
2
X
0
2
+
--------------------------
–
è ø
ç ÷
æ ö
×=
EQUATION562 V1 EN (Equation 159)
Setting of reach in resistive direction
Set the resistive reach independently for each zone, and separately for phase-to-phase
(R1PP), and phase-to-ground loop (R1PG) measurement.
Set separately the expected fault resistance for phase-to-phase faults (R1PP) and for
the phase-to-ground faults (RFPG) for each zone. Set all remaining reach setting
parameters independently of each other for each distance zone.
Section 3 1MRK504116-UUS C
IED application
244
Application manual