EasyManua.ls Logo

ABB RET670 - Page 307

ABB RET670
888 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Parallel line in service – Setting of zone1
With reference to section
"Parallel line applications", the zone reach can be set to 85%
of protected line.
Parallel line in service – setting of zone2
Overreaching zones (in general, zones 2 and 3) must overreach the protected circuit in
all cases. The greatest reduction of a reach occurs in cases when both parallel circuits
are in service with a single phase-to-ground fault located at the end of a protected line.
The equivalent zero-sequence impedance circuit for this case is equal to the one in
figure
131 in section "Parallel line applications".
The components of the zero-sequence impedance for the overreaching zones must be
equal to at least:
R
0E
R
0
R
m0
+=
EQUATION553 V1 EN (Equation 220)
X
0E
X
0
X
m0
+=
EQUATION554 V1 EN (Equation 221)
Check the reduction of a reach for the overreaching zones due to the effect of the zero
sequence mutual coupling. The reach is reduced for a factor:
0
0 1
2 1 0
m
f
Z
K
Z Z R
= -
× + +
EQUATION1426 V1 EN (Equation 222)
If the denominator in equation 222 is called B and Z0m is simplified to X0m, then the
real and imaginary part of the reach reduction factor for the overreaching zones can be
written as:
( )
( )
( ) ( )
2 2
0 Re
Re 0 1
Re Im
X m B
K
B B
×
= -
+
EQUATION1427 V2 EN
(Equation 223)
( )
( )
( ) ( )
2 2
0 Im
Im 0
Re Im
X m B
K
B B
×
=
+
EQUATION1428 V2 EN (Equation 224)
1MRK504116-UUS C Section 3
IED application
301
Application manual

Table of Contents

Other manuals for ABB RET670

Related product manuals