EasyManua.ls Logo

ABB RET670 - Page 437

ABB RET670
888 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
The protected winding will feed ground-fault (residual) current to ground faults in the
connected power system. The residual current fed from the transformer at external phase-
to-ground faults, is highly dependent of the total positive and zero-sequence source
impedances as well as the residual current distribution between the network zero-
sequence impedance and the transformer zero-sequence impedance. An example of this
application is shown in figure
194.
51N
alt
Three phase CT
summated
Single CT
WYE/DELTA or WYE/WYE
transformer
en05000490_ansi.vsd
ANSI05000490 V1 EN
Figure 194: Residual overcurrent protection application on a directly grounded
transformer winding
In this case the protection has two different tasks:
Detection of ground faults on the transformer winding, to which the protection is
connected.
Detection of ground faults in the power system, to which the protected winding is
connected.
It can be suitable to use a residual overcurrent protection with at least two steps. Step 1
shall have a short definite time delay and a relatively high current setting, in order to
detect and clear high current ground faults in the transformer winding or in the power
system close to the transformer. Step 2 shall have a longer time delay (definite or
inverse time delay) and a lower current operation level. Step 2 shall detect and clear
transformer winding ground faults with low ground-fault current, that is, faults close to
the transformer winding neutral point. If the current setting gap between step 1 and
step 2 is large another step can be introduced with a current and time delay setting
between the two described steps.
1MRK504116-UUS C Section 3
IED application
431
Application manual

Table of Contents

Other manuals for ABB RET670

Related product manuals