EasyManua.ls Logo

ABB RET670 - Page 439

ABB RET670
888 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
51N
Three phase CT
summated
Single CT
YN/D or YN/Y
transformer
Single phase-
to-ground fault
ANSI05000492_3_en.vsd
0
3I
alt
ANSI05000492 V3 EN
Figure 196: Step 1 fault calculation 1
This calculation gives the current fed to the protection: 3I
0fault1
.
To assure that step 1, selectivity to other ground-fault protections in the network a
short delay is selected. Normally, a delay in the range 0.3 – 0.4 s is appropriate. To
assure selectivity to line faults, tripped after a delay (typically distance protection zone
2) of about 0.5 s the current setting must be set so high so that such faults does not
cause unwanted step 1 trip. Therefore, a fault calculation as shown in figure
197 is made.
1MRK504116-UUS C Section 3
IED application
433
Application manual

Table of Contents

Other manuals for ABB RET670

Related product manuals