EasyManua.ls Logo

ABB RET670 - Page 665

ABB RET670
888 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Line voltage drop
The purpose with the line voltage drop compensation is to control the voltage, not at
the power transformer low voltage side, but at a point closer to the load point.
Figure 279 shows the vector diagram for a line modelled as a series impedance with
the voltage V
B
at the LV busbar and voltage V
L
at the load center. The load current on
the line is I
L
, the line resistance and reactance from the station busbar to the load point
are R
L
and X
L
. The angle between the busbar voltage and the current, is j. If all these
parameters are known V
L
can be obtained by simple vector calculation.
Values for R
L
and X
L
are given as settings in primary system ohms. If more than one
line is connected to the LV busbar, an equivalent impedance should be calculated and
given as a parameter setting.
The line voltage drop compensation function can be turned Enabled/Disabled by the
setting parameter OperationLDC. When it is enabled, the voltage V
L
will be used by
the Automatic voltage control for tap changer function, TR1ATCC (90) for single
control and TR8ATCC (90) for parallel control for voltage regulation instead of V
B
.
However, TR1ATCC (90) or TR8ATCC (90) will still perform the following two checks:
1. The magnitude of the measured busbar voltageV
B
, shall be within the security
range, (setting Vmin and Vmax). If the busbar voltage falls-out of this range the
line voltage drop compensation calculations will be temporarily stopped until the
voltage V
B
comes back within the range.
2. The magnitude of the calculated voltage V
L
at the load point, can be limited such
that it is only allowed to be equal to or smaller than the magnitude of V
B
,
otherwise V
B
will be used. However, a situation where V
L
>V
B
can be caused by a
capacitive load condition, and if the wish is to allow for a situation like that, the
limitation can be removed by setting the parameter OperCapaLDC to Enabled.
~
L
o
a
d
R
L
X
L
V
B
V
L
V
B
R
L
I
L
jX
L
I
L
Re
en06000487_ansi.vsd
ANSI06000487 V1 EN
Figure 279: Vector diagram for line voltage drop compensation
1MRK504116-UUS C Section 3
IED application
659
Application manual

Table of Contents

Other manuals for ABB RET670

Related product manuals