EasyManua.ls Logo

ABB RET670 - Page 697

ABB RET670
888 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
controlled in a parallel group with the reverse reactance method and with no circulation
(for example, assume two equal transformers on the same tap position). The load
current lags the busbar voltage V
B
with the power factor j and the argument of the
impedance Rline and Xline is designated j1.
V
B
jI
T
*Xline
V
L
Xline
Rline
Zline
I
T
I
T
*Rline
j
j
1
j
2
DV
en06000626_ansi.vsd
ANSI06000626 V1 EN
Figure 288: Transformer with reverse reactance regulation and no circulating current
The voltage DV=V
B
-V
L
=I
T
*Rline+j I
T
*Xline has the argument j2 and it is realised
that if j2 is slightly less than -90°, then V
L
will have approximately the same length as
V
B
regardless of the magnitude of the transformer load current I
T
(indicated with the
dashed line). The automatic tap change control regulates the voltage towards a set
target value, representing a voltage magnitude, without considering the phase angle.
Thus, V
B
as well as V
L
and also the dashed line could all be said to be on the target value.
Assume that we want to achieve that j
2
= -90°, then:
0
1 1
( )
90
0
1
0
1
90
90
j j j
j
j j
j j
+
-
D = ´
ß
D = ´ =
ß
- = +
ß
= - -
j j
j j
V Z I
Ve Ze Ie ZIe
EQUATION1983-ANSI V1 EN (Equation 429)
If for example cosj = 0.8 then j = arcos 0.8 = 37°. With the references in figure 288, j
will be negative (inductive load) and we get:
1MRK504116-UUS C Section 3
IED application
691
Application manual

Table of Contents

Other manuals for ABB RET670

Related product manuals