132kV Busbar
200/5
33kV Busbar
500/5
P Q
31.5 MVA
ANSI09000040-1-en.vsd
33kV 120V
/
3 3
V
AB
IED
ANSI09000040 V1 EN
Figure 307: Single line diagram for transformer application
In order to measure the active and reactive power as indicated in figure 307, it is
necessary to do the following:
1. Set correctly all CT and VT and phase angle reference channel PhaseAngleRef
(see section "Analog inputs") data using PCM600 for analog input channels
2. Connect, in PCM600, measurement function to LV side CT & VT inputs
3. Set the setting parameters for relevant Measurement function as shown in the
following table
213:
Section 3 1MRK504116-UUS C
IED application
758
Application manual