Table 219: VNMMXU Non group settings (basic)
Name Values (Range) Unit Step Default Description
VA_DbRepInt 1 - 300 Type 1 10 Cycl: Report interval (s), Db: In % of range,
Int Db: In %s
Operation Disabled
Enabled
- - Disabled Disbled/Enabled operation
VBase 0.05 - 2000.00 kV 0.05 400.00 Base setting for voltage level in kV
VA_Max 0.000 -
10000000000.000
V 0.001 300000.000 Maximum value
VA_RepTyp Cyclic
Dead band
Int deadband
- - Cyclic Reporting type
VA_LimHys 0.000 - 100.000 % 0.001 5.000 Hysteresis value in % of range and is
common for all limits
VA_AnDbRepInt 1 - 300 Type 1 10 Cycl: Report interval (s), Db: In % of range,
Int Db: In %s
VB_DbRepInt 1 - 300 Type 1 10 Cycl: Report interval (s), Db: In % of range,
Int Db: In %s
VB_Max 0.000 -
10000000000.000
V 0.001 300000.000 Maximum value
VB_RepTyp Cyclic
Dead band
Int deadband
- - Cyclic Reporting type
VB_LimHys 0.000 - 100.000 % 0.001 5.000 Hysteresis value in % of range and is
common for all limits
VB_AnDbRepInt 1 - 300 Type 1 10 Cycl: Report interval (s), Db: In % of range,
Int Db: In %s
VC_DbRepInt 1 - 300 Type 1 10 Cycl: Report interval (s), Db: In % of range,
Int Db: In %s
VC_Max 0.000 -
10000000000.000
V 0.001 300000.000 Maximum value
VC_RepTyp Cyclic
Dead band
Int deadband
- - Cyclic Reporting type
VC_LimHys 0.000 - 100.000 % 0.001 5.000 Hysteresis value in % of range and is
common for all limits
VC_AnDbRepInt 1 - 300 Type 1 10 Cycl: Report interval (s), Db: In % of range,
Int Db: In %s
1MRK504116-UUS C Section 3
IED application
767
Application manual