Table 220: VNMMXU Non group settings (advanced)
Name Values (Range) Unit Step Default Description
VA_ZeroDb 0 - 100000 m% 1 0 Zero point clamping in 0.001% of range
VA_HiHiLim 0.000 -
10000000000.000
V 0.001 260000.000 High High limit (physical value)
VA_HiLim 0.000 -
10000000000.000
V 0.001 240000.000 High limit (physical value)
VA_LowLim 0.000 -
10000000000.000
V 0.001 220000.000 Low limit (physical value)
VA_LowLowLim 0.000 -
10000000000.000
V 0.001 200000.000 Low Low limit (physical value)
VMagComp100 -10.000 - 10.000 % 0.001 0.000 Magnitude factor to calibrate voltage at 100%
of Vn
VA_Min 0.000 -
10000000000.000
V 0.001 0.000 Minimum value
VB_ZeroDb 0 - 100000 m% 1 0 Zero point clamping in 0.001% of range
VB_HiHiLim 0.000 -
10000000000.000
V 0.001 260000.000 High High limit (physical value)
VB_HiLim 0.000 -
10000000000.000
V 0.001 240000.000 High limit (physical value)
VB_LowLim 0.000 -
10000000000.000
V 0.001 220000.000 Low limit (physical value)
VB_LowLowLim 0.000 -
10000000000.000
V 0.001 200000.000 Low Low limit (physical value)
VB_Min 0.000 -
10000000000.000
V 0.001 0.000 Minimum value
VC_ZeroDb 0 - 100000 m% 1 0 Zero point clamping in 0.001% of range
VC_HiHiLim 0.000 -
10000000000.000
V 0.001 260000.000 High High limit (physical value)
VC_HiLim 0.000 -
10000000000.000
V 0.001 240000.000 High limit (physical value)
VC_LowLim 0.000 -
10000000000.000
V 0.001 220000.000 Low limit (physical value)
VC_LowLowLim 0.000 -
10000000000.000
V 0.001 200000.000 Low Low limit (physical value)
VC_Min 0.000 -
10000000000.000
V 0.001 0.000 Minimum value
Section 3 1MRK504116-UUS C
IED application
768
Application manual