Table 221: VMMXU Non group settings (basic)
Name Values (Range) Unit Step Default Description
VAB_DbRepInt 1 - 300 Type 1 10 Cycl: Report interval (s), Db: In % of range,
Int Db: In %s
Operation Disabled
Enabled
- - Disabled Disbled/Enabled operation
VBase 0.05 - 2000.00 kV 0.05 400.00 Base setting for voltage level in kV
VAB_Max 0.000 -
10000000000.000
V 0.001 500000.000 Maximum value
VAB_RepTyp Cyclic
Dead band
Int deadband
- - Cyclic Reporting type
VAB_AnDbRepInt 1 - 300 Type 1 10 Cycl: Report interval (s), Db: In % of range,
Int Db: In %s
VBC_DbRepInt 1 - 300 Type 1 10 Cycl: Report interval (s), Db: In % of range,
Int Db: In %s
VBC_Max 0.000 -
10000000000.000
V 0.001 500000.000 Maximum value
VBC_RepTyp Cyclic
Dead band
Int deadband
- - Cyclic Reporting type
VBC_AnDbRepInt 1 - 300 Type 1 10 Cycl: Report interval (s), Db: In % of range,
Int Db: In %s
VCA_DbRepInt 1 - 300 Type 1 10 Cycl: Report interval (s), Db: In % of range,
Int Db: In %s
VCA_Max 0.000 -
10000000000.000
V 0.001 500000.000 Maximum value
VCA_RepTyp Cyclic
Dead band
Int deadband
- - Cyclic Reporting type
VCA_AnDbRepInt 1 - 300 Type 1 10 Cycl: Report interval (s), Db: In % of range,
Int Db: In %s
Table 222: VMMXU Non group settings (advanced)
Name
Values (Range) Unit Step Default Description
VAB_ZeroDb 0 - 100000 m% 1 0 Zero point clamping in 0.001% of range
VAB_HiHiLim 0.000 -
10000000000.000
V 0.001 450000.000 High High limit (physical value)
VAB_HiLim 0.000 -
10000000000.000
V 0.001 420000.000 High limit (physical value)
VAB_LowLim 0.000 -
10000000000.000
V 0.001 380000.000 Low limit (physical value)
VAB_LowLowLim 0.000 -
10000000000.000
V 0.001 350000.000 Low Low limit (physical value)
Table continues on next page