© Agilent Technologies 1989–2002 Agilent 3070 / 79000 Site Preparation 10-98
Chapter 10: Site Preparation – Power Requirements for Older Systems: Series 3 Power Requirements and Connections (Prior to May 2000)
* Three current-carrying conductors
*** Pigtail required (Chapter 10,
Connecting a Pigtail
to the E1135C PDU.)
Table 10-15 Single-phase Wye with neutral (05B, 05G, 05K)
System Type
327X / 79000 317X 307X
Breaker Size in Amps
1
[30] 20 [30] 20 [50] 30
Wire Size mm
2
(American Wire Gauge - AWG)
2
[6 (10)] 4(12)* [6 (10)] 4(12)* [16 (6)]*** 6(10)
1. Breaker size based on 125 percent of maximum rms current
2. Wire size based on multiconductor cables