EasyManua.ls Logo

Artesyn iHP - Specification Summary

Artesyn iHP
202 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
iHP Manual 11 | P a g e
iHP Owners Manual
The simplest way to get started is to use the Power Pro Connect Module (PPCM) to establish a link to the
supply. The PPCM allows the user to quickly establish a connection with the power supply with a Web based
GUI and set up the power supply. The configuration of the supply can be set up to run autonomously when
powered on, controlled via rear panel digital and analog input and outputs, or actively controlled via the
PPCM.
For more advanced users developing their own software control, the PPCM is not required and the supply can
be directly interfaced via the users preferred standard communications protocols, including CANbus, Ethernet
and RS485.
1.3 Specification Summary
Tables 1-1 and Table 1-2 below summarize the 24K and 12K input parameters, followed by Table 1-3 outlining
the general Module specifications
Table 1-1
iHP24 Electrical Specifications
Input Parameter
19” Rack 24 KW strapped as 3-phase
380/480 Vac Nominal (iHP24H3A/L)
19” Rack 24 KW strapped as 3-phase
208/240 Vac Nominal (iHP24L3A/L)
Input range
342 Vac to 528 Vac
(Nominal rating 380/480 Vac)
187.5 Vac to 264 Vac
(Nominal rating 208/240 Vac)
Number of phases
3-phase (Wye or Delta) 4 wire total (3-phase and 1 protective earth ground)
Frequency
47-63 Hz
Phase detection
Loss of phase will inhibit unit off. Housekeeping/comms must continue with phase loss.
Max current/phase
51 A @ 342 Vac
40 A @ 432 Vac
84 A @ 187.5 Vac
Under voltage detection
Nominal input locked on at turn-on. Under voltage shutdown at 15% below nominal.
Turn-on at 12% below nominal. Not to interfere with SEMI F47 specs.
Current inrush
2.5 x Max input current
Power factor
> 0.98 @ full load and nominal line
Harmonic distortion
THD < 13%, PWHD < 22% (refer to EN 61000-3-12)
Line interruption
Designed to meet SEMI F47-0706, 53, 58, S14 at nominal input voltages
Input leakage current
< 2.5 mA (Note for fixed condition 3rd edition leakage = 5 mA)
Power switch
Front panel power switch provided
Input protection
Internal fuse (not user serviceable)
Input overvoltage protection
Up to 115% of nominal input shall not damage unit
Phase imbalance
≤ 5%
Rack parallel
Up to 6 racks (144 KW)
Efficiency
> 90% @ 3P 380 Vac full load
> 91% @ 3P 480 Vac full load
> 90% @ 3P 208 Vac full load
> 91% @ 3P 240 Vac full load
Standby voltage
5 V
Standby regulation
4.75 - 5.25 V
Standby max current
1 A

Table of Contents