iHP Manual 48 | P a g e
Use to control the output voltage by applying 0 to 10V
to this pin. This pin will function when the module is
configured to Analog Voltage Source.
Use to control the output voltage by applying 0 to 5V to
this pin. This pin will function when the module is
configured to Analog Voltage Source.
Use to control the output current by applying 0 to 10V
to this pin. This pin will function when the module is
configured to Analog Current Source.
Use to control the output current by applying 0 to 5V to
this pin. This pin will function when the module is
configured to Analog Current Source.
Signal to Inhibit the module
Ground reference for J1 signals.
Signal to Enable the module
Signal to notify user that Fault occurred.
4.2.1.1.1 Analog Voltage Programming
0-10VEXT_VPROG (J1 Pin1) and 0-5VEXT_VPROG (J1 Pin2) are used to program the output voltage by applying
external voltages. Analog voltage programming will work if the module configuration is in analog voltage
source.
Please note that 0-10VEXT_VPROG and 0-5VEXT_VPROG cannot be used simultaneously:
If user will use 0-10VEXT_VPROG, 0-5VEXT_VPROG should be floating.
If user will use 0-5VEXT_VPROG, 0-10VEXT_VPROG should be floating.
When utilizing signal, 0-10VEXT_VPROG, apply 0V to 10V between J1 pin 1 (0-10VEXT_VPROG) and J1 pin 8
(SYS_RTN). Table 4-4 shows the corresponding output voltage when utilizing this signal.
Table 4-4
Corresponding Output Voltage
5% Nominal Output Voltage