iHP Manual 24 | P a g e
iHP Owners Manual
Table 2-1
Size
Temperature Rating
AWG
60°C
75°C
90°C
Types RUW, T, TW, UF
Types FEPW, RHW, RH, RUH,
THW, THWN, XHHW, ZW
Types TA, TBS, SA, AVB, SIS,
FEP, FEPB, RHH, THHN, XHHW
14
20
20
25
12
25
25
30
10
30
35
40
8
40
50
55
6
55
65
75
4
70
85
95
3
85
100
110
2
95
115
130
1
110
130
150
1/0
125
150
170
2/0
145
175
195
3/0
165
200
225
4/0
195
230
260
2.5.1 AC Input Wiring
The iHP system is designed for permanent connection to the AC power with a readily accessible safety
disconnect device.
Warning! - A safety ground wire must be connected to the unit through the chassis ground
stud show in Section 1.2.4. An appropriate ring terminal for M6 stud and the wire gauge
must be used.
The input configuration should be confirmed prior to wiring any AC power into iHP system. The figure below
shows the location of the label to confirm the AC configuration.