Module Grouping should be the same in each rack
RACK SYNCRONIZED OFF should be enable
Series Operation Safety Accessibility Restrictions
Secondary Signal and Power Output
Series up to
300Vdc
(MOPP)
Series up to
400Vdc
(MOOP & ITE)
Series up to
600Vdc
(MOPP)
Series up to
800Vdc
(MOOP)
Series up to
1000Vdc
(ITE)
Safe to access if the total output voltage is equal or less than 60V
Not safe to access if the total output voltage is more than 60V.
Requires Enclosure for safety protections
Safe to access if the total output voltage is equal or less than 60V
Not safe to access if the total output voltage is more than 60V.
Requires Enclosure for safety protections