EasyManua.ls Logo

BW Technologies MicroDock II - Not Found

BW Technologies MicroDock II
100 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
57
MicroDock II
Gas Conflicts
2. Press C or C to move to the gas that is in conflict.
3. Press
C sel to access the inlet field. automatically displays
on the left side of the inlet.
4. Press
C or C to scroll to the desired inlet (1-5).
5. When the required inlet value displays, press
C sel to confirm
the selection and exit the field. no longer displays to the right
of the inlet, indicating the conflict has been resolved.
Note
If
C sel is not pressed within 30 seconds, the base station
automatically defaults to the inlet it has selected.
Unsuccessful Conflict Resolution: If the conflict is not resolved by
selecting a different inlet, refer to the following:
Ensure that the selected inlet is correct.
Ensure the gas cylinder that is attached to the selected inlet is
correct.
Press
C OK to accept the base station’s default selection.
Not Found
If a value of 1 or more displays before Not Found, the base station is
unable to locate the required gas type for a specific sensor on the detec-
tor.
Press
C cancel to exit the gas conflict screen and return to normal
operation. A bump test or calibration will not be performed.
To define the gas inlets, complete the following.
1. Press
C more in the gas conflicts screen to access the gas
type/inlet screen to view which gas type(s) cannot be found.

Table of Contents

Other manuals for BW Technologies MicroDock II